DF-HEAT Direct-Fired Heating System - Model ZDF
|
|
|
The ZDF Direct Fired systems are flexible, cost-effective units for indoor or outdoor space heating, make-up air, and ventilation applications. Superior tube frame construction and stainless steel burners deliver decades of reliable service. The ZDF from Sierra can provide up to 16,000 CFM of warm, fresh and clean air to your building. | |
|---|---|---|---|
| ZDF SERIES MODEL | CFM RANGE | MBH INPUT RANGE | BASIC UNIT FOOTPRINT LxWxH | AVAILABLE ARRANGEMENTS | APPROVALS | AVAILABLE ACCESSORIES |
|---|---|---|---|---|---|---|
| 035 | 2,000-3,500 | 329-514 | 68"x42"x36" | Horizontal or Vertical | ANSI, FM, IRI | Inlet Hood, V-Bank Filter Section, and Mixing Dampers with Return Air Flow Station |
| 070 | 3,750-7,000 | 329-1,027 | 76"x52"x40" | |||
| 110 | 7,250-11,000 | 329-1,615 | 82"x64"x48" | |||
| 160 | 11,500-16,000 | 329-1,933 | 92"x64"x48" |
| Control System | Application | Includes: |
|---|---|---|
| MDT |
Modulating Discharge Temperature Control |
Discharge air sensor mounted in unit discharge with remote mounted 3 gang box cover including manual potentiometer to enable unit and adjust temperature setpoint, Fan On Light, Burner On Light, and Cool On Light. Additional potentiometer is provided if optional return air damper section for manual or mixed air control is ordered. |
| MRT |
Modulating Room Temperature Control |
Discharge air sensor mounted in unit discharge with remote mounted 3 gang box cover including manual potentiometer to enable unit and adjust temperature setpoint, Fan On Light, Burner On Light, and Cool On Light. Also includes RS-std room sensor (does not allow remote room setpoint adjustment). Additional potentiometer is provided if optional return air damper section for manual or mixed air control is ordered. |
| MRT-Pro | Modulating Room Temperature Control with RS-Pro room sensor allowing after hours unit enable, room setpoint adjustment, and digital temperature readout. | Discharge air sensor mounted in unit discharge with remote mounted RS-Pro room sensor with push buttons for room setpoint adjustment and digital temperature readout. On units with optional return air damper section a remote mounted 3 gang box cover is provided with potentiometer for manual or mixed air control. |
| MRT-Expert | Modulating Room Temperature Control with BACview controller allowing after hours unit enable, room setpoint adjustment, operating feedback, monitoring of alarm status and digital temperature readout with RS-std room sensor. | Discharge air sensor mounted in unit discharge with remote mounted BACview controller to set space temperature, operating schedules, and optional damper control setpoints. Service information, operating feedback and alarm status can also be monitored. Also includes a remote mounted RS-std room sensor. |
| VDT-Expert | Modulating Discharge Temperature Control with BACview controller allowing after hours unit enable, operating feedback, and monitoring of alarm status. | Discharge air sensor mounted in unit discharge with remote mounted BACview controller to set discharge temperature setpoint and operating schedules. Service information, operating feedback, and alarm status can also be monitored. |